A checking aid β not a substitute for a competent person, a site assessment, or BS 7671 itself.
Limits shown are the published values of BS 7671:2018+A2:2022 and IET Guidance Note 3.
Always confirm against the current regulations and the specific installation. Coding requires professional judgement.
Verify an EICR PDF
Drop an EICR report below (or tap to choose). It reads the schedule of test results and checks each circuit against BS 7671 β the report never leaves your device.
πβ‘
Drop an EICR PDF here
or tap to choose a file
Maximum earth-fault loop impedance (Zs)
BS 7671 Tables 41.3 / 41.4 (Cmin 0.95, Uβ 230 V). For MCBs / RCBOs the limit is set by the magnetic trip.
The tabulated value assumes conductors at operating temperature. A reading taken cold should sit at or below the 0.8Γ "rule-of-thumb" figure (GN3) β that's what the pass/fail uses. If the circuit is RCD-protected, fault protection is by the RCD instead β see the RCD tab (Zs β€ 50 β Iβn). Fuse presets aren't built in yet; use BS 7671 Table 41.2/41.4 for those.
RCD operation & disconnection times
BS 7671 411.3 / Table 41.1 and GN3. Test at 0Β° and 180Β°, record the longer time.
A 30 mA RCD for additional protection must trip β€ 300 ms at 1ΓIβn and β€ 40 ms at 5ΓIβn. (A no-test-button or failed operation is a code β see Coding.)
End-to-end resistances (step 1 of the 3-step test). Line & neutral should match; r2 depends on the CPC size.
Healthy ring: r1 β rn, and r2 β (line Γ· cpc) Γ r1 (e.g. 2.5/1.5 mmΒ² β r2 β 1.67 Γ r1). Cross-connected readings at each socket should be near-uniform; the expected R1+R2 = (r1 + r2) β 4. A high/odd reading points to a break, spur, or cross-connection.
Observation coding β C1 Β· C2 Β· C3 Β· FI
Per IET Guidance Note 3 & Best Practice Guide 4. The code depends on the actual situation β these are typical examples, not rulings.
C1 Danger present
Risk of injury β immediate remedial action required. (Exposed live parts, incorrect polarity, unsafe conductor.)
C2 Potentially dangerous
Urgent remedial action required. (No/inadequate earthing or bonding, no CPC at an accessory, damaged accessory.)
C3 Improvement recommended
Not a fail on its own. (No RCD where now recommended but not required at install, no SPD, old cable colours with a warning notice.)
FI Further investigation
Required without delay β something couldn't be fully assessed and may reveal a danger.
Overall: the report is UNSATISFACTORY if there is any C1, C2 or FI. C3 items alone β still Satisfactory (but recorded).
Common observations β typical code
Curated examples per BS 7671:2018+A2:2022 / GN3 / BPG4 β guidance only, not rulings. The Type AC β Type A, SPD and AFDD items are amendment-driven and usually C3, but escalate where the circuit specifically needs it (e.g. a Type AC RCD on an EV charge point or known DC-fault equipment is typically C2). Where an item could go either way, the inspector's judgement of the actual risk decides β and if it can't be assessed, it's FI.